Development and experimental study of a compact silica gel-water adsorption chiller for waste heat driven cooling in data centers
Energy Conversion and Management, ISSN: 0196-8904, Vol: 300, Page: 117985
2024
- 10Citations
- 22Captures
- 1Mentions
Metric Options: Counts1 Year3 YearSelecting the 1-year or 3-year option will change the metrics count to percentiles, illustrating how an article or review compares to other articles or reviews within the selected time period in the same journal. Selecting the 1-year option compares the metrics against other articles/reviews that were also published in the same calendar year. Selecting the 3-year option compares the metrics against other articles/reviews that were also published in the same calendar year plus the two years prior.
Example: if you select the 1-year option for an article published in 2019 and a metric category shows 90%, that means that the article or review is performing better than 90% of the other articles/reviews published in that journal in 2019. If you select the 3-year option for the same article published in 2019 and the metric category shows 90%, that means that the article or review is performing better than 90% of the other articles/reviews published in that journal in 2019, 2018 and 2017.
Citation Benchmarking is provided by Scopus and SciVal and is different from the metrics context provided by PlumX Metrics.
Example: if you select the 1-year option for an article published in 2019 and a metric category shows 90%, that means that the article or review is performing better than 90% of the other articles/reviews published in that journal in 2019. If you select the 3-year option for the same article published in 2019 and the metric category shows 90%, that means that the article or review is performing better than 90% of the other articles/reviews published in that journal in 2019, 2018 and 2017.
Citation Benchmarking is provided by Scopus and SciVal and is different from the metrics context provided by PlumX Metrics.
Most Recent News
Recent Findings in Data Centers Described by Researchers from Shanghai Jiao Tong University (Development and Experimental Study of a Compact Silica Gel-water Adsorption Chiller for Waste Heat Driven Cooling In Data Centers)
2024 FEB 07 (NewsRx) -- By a News Reporter-Staff News Editor at Information Technology Daily -- A new study on Information Technology - Data Centers
Article Description
In recent years, data centers have experienced rapid construction, leading to a significant surge in energy consumption, and cooling systems have emerged as prominent energy consumers of data centers. Among the cooling technologies, liquid cooling allows higher cooling circuit temperatures and provides potential for heat recovery. As a thermally driven cooling technology, adsorption refrigeration systems offer an alternative way to compression refrigeration systems by utilizing low-grade waste heat from liquid-cooled circuits to produce chilled water for air-cooled components. In this study, a compact silica gel-water adsorption chiller is developed for a small modular data center and experimentally investigated under extremely low driving temperatures. Under the typical summer conditions with the hot/cooling/chilled water inlet temperatures of 50 °C/30 °C/23 °C, the adsorption chiller achieves the cooling power of 4.9 kW and the COP of 0.50. When the cooling water inlet temperature changes from 32 °C to 24 °C, both the cooling power and COP show significant improvements, from 3.04 kW to 10.50 kW and from 0.44 to 0.66, respectively. Moreover, the increase of the hot water inlet temperature from 48 °C to 56 °C can enhance the cooling power to some extent, while the chilled water inlet temperature has little influence on the performance. The experimental results demonstrate the feasibility and performance of the developed adsorption chiller in data center waste heat driven cooling. Besides, potential adsorbents and possible optimization strategies are presented for performance improvement based on adsorption potential method.
Bibliographic Details
http://www.sciencedirect.com/science/article/pii/S0196890423013316; http://dx.doi.org/10.1016/j.enconman.2023.117985; http://www.scopus.com/inward/record.url?partnerID=HzOxMe3b&scp=85180374063&origin=inward; https://linkinghub.elsevier.com/retrieve/pii/S0196890423013316; https://dx.doi.org/10.1016/j.enconman.2023.117985